Galaxy External Telecoms Connections and Configuration – RS485
Connect the WebWay panel interface 485 A and B to the Galaxy Dimension connection terminals A and B (Labelled
‘RS485 Line 1’ in the Galaxy Engineer’s Manual PCB Layout). ). NOTE – Emulation of a Galaxy Ethernet module allows
the SPT to be located anywhere on Bus 1. The SPT must be connected to Data Bus 1 and NOT Bus 2. Is labelled as S3
on the Galaxy 500 Series Variant. Bus 1 is also available on terminals labelled S1 & S2 on Galaxy 18 series as well as
the A & B data line terminations. You will also need RTN connected to a GND in the panel.
Connect the WebWay PWR + and - to the GND and +12V terminals on the Galaxy Panel.
Galaxy External Telecoms panel configuration
Go to Menu 56
Select External Telecoms (Menu 5). Older panels may support an Internal Telecom Module (Menu 1) which may
be classed as an External Module.
Select Format (Option 1)
Enter SIA (Option 2), <Level 3(0-4)>
Press Enter
Under the trigger events settings you define which events the panel will report.
Note: it is recommended that the additional Triggers are selected:
Select 10 – Settings <ON> (Default OFF)
Select 18 – Zone Restorals <ON> (Default OFF)
Select Tel No. 1 (Option 2)
Set Phone Number – 01234 567890 (any valid phone number is acceptable)
Select Account number (Option 3)
Enter <_______> (Site ID)
Go to Remote Access (Option 12)
Select Access Period <Anytime>
Select Mode <Direct Access>
Use escape to return to Engineer Mode. You need to fully exit Engineering to find the WebWay as a Comms module, we
also emulate a Keypad, typically Comms Module 005 and Keypad 011 – varies between panels. On older panels with no
External Telecoms option the Comms Module will be 001.