n.b. WebWay Pins will not signal an event unless an electrical change of state occurs. Therefore all connected control
equipment should be tested from alarm source and NOT by removing the alarm cable from the SPT pin input.
I&HAS applications: When used in I&HAS applications PIN Inputs 9-16 are always programmed as simple high low
inputs and PIN Inputs 1-8 can be individually programmed as END OF LINE (EOL) or simple HIGH/LOW inputs. This
needs to be specifically requested so it can be enabled on the device.
Hard wired Inputs 1-8 configured as ‘end of line’ (EOL)
Alarm state 10k +/- 5%
Restore state 14k7 +/- 5%
Open circuit Loop > 100k ohms
Short circuit Loop < 5 ohms
Tamper conditions - Loop between > 5 ohms & < 10k ohms -5%
- Loop between > 10k ohms + 5% & < 14k7 ohms -5%
- Loop between > 14k7 ohms + 5% & < 100k ohms
If required the alarm and restore conditions may be reversed in the SPT configuration
n.b. EOL pins cannot function with a +12V reference, it must be a 0V reference.