Galaxy Serial (RS232) Connections and Configuration
Connect the WebWay panel interface 232 R and T to the Galaxy printer interface RX and TX with the reverse of T to RX
and R to TX connections. You will also need RTN connected to a GND in the panel.
Connect the WebWay PWR + and - to the GND and +12V terminals on the Galaxy Panel.
Galaxy G3 panel configuration
Galaxy Internal RS232 module
Engineer menu 56
Menu 6 - Int RS232 1
Select Mode - Direct
Select Format SIA
Enter SIA (Option 2), <Level 3(0-4)>
Note: it is recommended that the additional Triggers are selected:
Select 10 <ON>
Select 18 <ON>
Enter Account number <_______> Site ID
Select Comms Setup
Enter Baud rate - 57600
Enter Data bits - 8
Enter Stop bits - 1
Select Parity - No parity
Escape to return to Engineer Mode. Exit Engineering fully in order for the panel and the SPT to begin communication.
NOTE: The Int RS232 module is not recognised by the Galaxy as a communications module therefore the keypad will not
provide a “module added” indication.